5
- 500 Horsepower Industrial Fan and Pump Drive
The P7 is designed for
variable torque applications like Fans and Centrifugal
Pumps. It is supplied with V/f control and Normal Duty
overload rating of 110% for one minute. Network
communications, plug-in I/O cards, and power/packaging
options are available. With an optional phase-shifting input
transformer, the P7 dual-diode bridge can be operated in
12-pulse rectification mode, reducing input current harmonic
distortion.
The P7 / Configured package
provides a P7 drive in a NEMA 1 or NEMA 12 FVFF enclosure,
with space for factory-mounted and wired options, such as
reactors, filters, circuit breakers, fuses, network
communications and I/O cards etc.
The P7 / Bypass package provides
a P7 drive and 3-contactor bypass in a NEMA 1 or NEMA 12
FVFF enclosure, of sufficient size to mount and wire
commonly selected options such as filters, fuses, network
communications and I/O cards.
Models
and Ratings |
Specifications
and Features for P7 Drive
|
|
For industrial
applications such as centrifugal fans and pumps, the
P7 drive is an ideal choice. The drive is provided
in Normal Duty ratings with 110% overload
capability. V/f control mode, network communication
options, and an array of input/output options are
available.
The P7 is
factory-programmed and ready to run. For operational
simplicity and clarity, the LCD operator display has
5 lines x 16 characters. It can be set to any of 6
languages. The keypad is intuitive and includes
parameter copying to move a chosen set of parameters
from one drive to another. If the application
requires programming, the P7 makes it easy.
Parameters are grouped in easy to use sets; quick
start and advanced. To enhance parameter and data
management, DriveWizard software for the PC is
available at no charge, for upload/download,
trending, and graphing.
This drive is designed for tough industrial
environments. It is rugged and reliable, with an
MTBF of 28 years. A variety of enclosure options
provide the right environmental protection.
Providing the right power requirements is also easy
with 208/240 and 480 volt ratings, built-in bus
choke above 30 HP, common bus capability, and other
energy savings options. Other features include motor
auto-tuning and configurable options such as circuit
breakers and fuses.
The P7 supports the industry's open architecture,
open connectivity demands with network
communications choices such as DeviceNet, Profibus-DP,
and others. Drive coordination with other equipment
is simplified with inputs and outputs for 4 to 20 mA,
0-10 V, and an assortment of programmable contacts.
With an optional phase-shifting input transformer,
the P7 dual-diode bridge can be operated in 12-pulse
rectification mode, reducing input current harmonic
distortion factor by over 90%. With lower EMI/RFI
emission and lower total harmonic distortion
contribution, the P7 meets or exceeds the generally
accepted power quality standards. Inherent motor
protection features resulting from low noise/low
carrier technology provides for longer lead lengths
without additional motor protection devices.
The optional P7/Bypass package is a 3-contactor
style bypass, allowing motor operation from the
drive or across the line. This facilitates drive
maintenance while the motor continues to operate.
The P7 has been designed to provide the features and
options commonly needed for fan and pump
applications.
Peformance
Features
- Ratings:
5-150 HP, 208 VAC
5-150 HP, 230 / 240 VAC
5-500 HP, 480 VAC
5-250 HP, Bypass
- Overload
capacity: nominal 110% for 60 sec (150%
peak)
- Starting
torque: 100% at 3 Hz
- DC
injection braking: at start or stop,
adjustable, current-limited (anti-windmilling)
- Motor
preheat function
- Adjustable
accel/decel: 0.1 to 6000 sec.
- Controlled
speed range: 40:1
- Critical
frequency rejection: 3 selectable,
adjustable bands
- Torque-limiting:
30-180%
- Energy $aving
control
- Torque
boost: full range, auto
- Power loss
ride-thru: 2 sec
- Inertia
ride-thru
- Auto
restart after power loss or resettable
fault, selectable, programmable
- Feedback
signal loss detection
- Serial
communications loss detection
- "Up/Down"
floating point control capability
- Stationary
motor auto-tuning
- Sleep
function
- Run-permissive
input
Protective
Features
- Current-limited
stall prevention
- Heat sink
over-temperature, speed fold-back
- Bi-directional
start into rotating motor
- Current-limiting
DC bus fuse
- Optically-Isolated
controls
- Short
circuit protection: Phase-phase and
phase-neutral
- Ground
fault protection
- Short
circuit withstand rating: 65K RMS, 100K
RMS with bus reactor
- Electronic
motor overload: UL
- Current
limit
- Fault
display: last 10 faults
- Fault
circuit: OC, OV, OT
- Over
torque and under torque protection
- Reverse
prohibit selectability
Inputs and
Outputs
- Output
contacts: One form C and two
programmable form A
- Input
terminals: 5 programmable multi-function
input terminals
- Fault
input: Programmable
- Remote
speed command: 0-10 VDC or 4-20 mA,
direct or reverse-acting
- Analog
outputs: Programmable, two, 0-10 VDC
|
Design
Features
- LCD keypad
display, 5 lines x 16 characters,
backlit, 6 languages, copy function
- Multi-step
speed settings: 5 available
- Setpoint
(PI) control
- 32-bit
microprocessor logic
- Nonvolatile
memory, program retention
- Displacement
power factor: 0.98
- Output
frequency: 0.1 to 120 Hz
- Frequency
resolution: 0.06 Hz
- Frequency
regulation: 0.1%
- Control
Terminal Board: Quick disconnect
- Carrier
frequency: selectable to 15 kHz
- 3% DC bus
reactor:
30-150 HP, 208 VAC; 30-150 HP, 240 VAC;
40-500 HP, 480 VAC; optional on lower
ratings
- 24 VDC
control logic, PNP / NPN selectable
- Transmitter/Option
power supply
- Input/output
terminal status
- Timer
function: Elapsed time, Delay on start,
Delay on stop
- RS-422/485
port: Modbus protocol
- Volts/hertz
ratio: Preset and programmable V/Hz
patterns
- Meter
Functions: Volt, amp, kilowatt, elapsed
run time, speed command
- NEMA 1 or
protected chassis
- UL, cUL
listed and CE marked; IEC 146;
- MTBF:
exceeds 28 years
- DriveWizard
upload/download and monitoring/graphing
software
Service
Conditions
- Ambient
Temperature:
-10°C to 40°C NEMA 1, 45°C protected
chassis (14°F to 104°F, 113°F)
- Humidity:
95% RH, non-condensing
- Altitude:
3300 ft; higher by derate
- Input
voltage: +10%/-15%
- Input
frequency: 50/60 Hz ± 5%
- 3-phase,
3-wire, phase sequence insensitive
Bypass
Features
- Input,
output, and bypass contactors
- Circuit
breaker disconnect (MCP)
- Thermal
motor overload relay, class 20
- 115 VAC
control transformer, fused
- Drive/Bypass
selector
- Hand/Off/Auto
selector
- Normal/Test
selector
- Pilot
lights
- Selectable
auto transfer to bypass on drive fault
- Run mode
and Fault contacts
- Safety
circuit interlock
- Control
and safety circuit terminal strip
- Customer
Use, 115 VAC, 100 VA
|
|
|
|
|
|
|
|
|
|
|
|
PARTECH
INDUSTRIES, INC.
|
|
5773
NW 151 Street, Miami Lakes, Fl 33014 U.S.A Tel
305-751-0160 Fax 305-757-9809
e-mail: sales@partech.us
|
|
|